[Submitted on 30 Jul 2026]
Abstract:Digital substations that comply with IEC 61850 have improved the operational efficiency of modern power systems. However, adversaries can abuse IEC 61850 communication to manipulate circuit breaker operations in substations, which can result in severe system impacts. These cyber attacks are crafted based on broader multi-phase strategies. The existing intrusion detection systems (IDSs) often flag only isolated symptoms. Thus, there is a lack of context in the attack phase to support the deployment of mitigation measures. This paper proposes Substation Cyber Attack Strategy Phasing (SubCASP), a Hidden Markov Model(HMM)- based method that fuses IDS data logs to infer the current attack phase, next attack phase, and retrospective attack path. The attack phases are derived from an ATT&CK-based threat modeling. The SubCASP model is trained and evaluated on a reproducible attack-graph dataset. Test results are presented to demonstrate the robustness of SubCASP for various IDS observability levels and missing IDS data logs scenarios.
Submission history
From: Akila Herath [view email]
[v1]
Thu, 30 Jul 2026 04:17:40 UTC (732 KB)
0 Comments
Log in to join the conversation.No comments yet. Be the first to share your thoughts.